Load bank testing is one of the best ways to confirm a standby generator is ready, but how often you need it depends on two things: what your codes and authorities require, and what makes sense for your equipment and how critical your power is. The answer is not always the same for both.
Facilities with emergency power systems are often covered by NFPA 110 and related codes, which set requirements for exercising and testing. According to the NFPA 110 guidance on our NFPA 110 compliance page, Level 1 and Level 2 generators need a monthly test under available load for a minimum of 30 minutes. (A Level 1 generator is one whose failure could result in death or serious injury. A Level 2 generator is one whose failure would not result in life-threatening injury.) A monthly test is successful when the generator either reaches the minimum exhaust gas temperature listed in the owner's manual, or runs at normal temperature at no less than 30% of its nameplate kilowatt rating.
If a generator fails the monthly test, it should be operated on a load bank for two continuous hours each year: 30 minutes at 25% of nameplate kilowatt rating, 30 minutes at 50%, and 60 minutes at 75%. Healthcare and other regulated facilities may have additional requirements from their own codes and accrediting bodies. Your local authority having jurisdiction has the final say, so confirm the rules that apply to your site.
Even where codes do not require it, many owners load test on a regular schedule because it is the only way to know a generator can carry its load. Consider more frequent testing when:
Many of our commercial and industrial clients choose an annual 2-hour load bank test, along with an annual major service and an annual minor service, plus a 4-hour load bank test every three years. Power-critical clients often pair an annual major service and 2-hour load bank test with quarterly minor services. We build each plan around your equipment, your requirements and your risk.
Whatever schedule you follow, keep every test report. Records support inspections and audits and help you track performance trends year over year.
Managed Generator Services has more than 25 years of experience and factory-trained, certified technicians serving 12 states from New Jersey to Florida. Our team is on call 24/7 with typical response times of 2 to 4 hours, and we service all major makes, models and sizes. We can review your requirements and recommend a load bank testing schedule that covers compliance and keeps your generator ready.